Skip to content
CVE Tracker
Back

CVE-2014-9196

Eaton’s Cooper Power Series Form 6 Control and Idea/IdeaPlus Relays with Ethernet

High7.6EPSS 2.5%
Published
Updated
Reserved
Assigned by
icscert

Description

Eaton Cooper Power Systems ProView 4.0 and 5.0 before 5.0 11 on Form 6 controls and Idea and IdeaPLUS relays generates TCP initial sequence number (ISN) values linearly, which makes it easier for remote attackers to spoof TCP sessions by predicting an ISN value.

Scores

CVSS scores of CVE-2014-9196, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)2.0High7.6AV:N/AC:H/Au:N/C:C/I:C/A:C
NVDNVD · Modified2.0High9.3AV:N/AC:M/Au:N/C:C/I:C/A:C
EPSS (exploitation in 30 days)
2.5% · top 15% of all CVEs (3 Nov 2026)

Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.6.

Weakness

Affected products

  • Eaton’s Cooper Power Systems · Series Form 6

    • affected Pro View 4.0 – ≤ Pro View 5.0
  • Eaton’s Cooper Power Systems · Idea/IdeaPLUS relays

    • affected Pro View 4.0 – ≤ Pro View 5.0

What to do

Solution: Eaton’s Cooper Power Systems division has developed ProView 5.0 Revision 11 software that mitigates this vulnerability, and the Form 6 control version was released on June 12, 2015. Idea/IdeaPLUS relay ProView software versions began to be posted on June 30, 2015. ProView 5.0 Revision 11 will be compatible with any hardware and firmware Versions 5.0 and higher. Versions below 5.0 may be updated with the appropriate and corresponding hardware upgrades. Information on how to obtain and install these available remedies is available at: http://www.cooperindustries.com/content/public/en/power_systems/resources/securitysupport.html For additional technical information, please contact Eaton’s Cooper Power Systems at: https://www.eaton.com/cybersecurity

Workaround: No authentication mechanism was used for new socket connections to SCADA protocol listening ports on the Form 6 control and Idea/IdeaPLUS relays. The effects of exploiting this vulnerability are the same as the effects of an attacker connecting directly to the control or network and listening for or initiating a new session, without exploiting any vulnerabilities. This underscores the importance of deploying network segmentation and isolation on the control system network. By ensuring that controls are not accessible from external networks and that appropriate physical security measures are provided at network access points, risks associated with this vulnerability are greatly minimized. Eaton’s Cooper Power Systems recommends that asset owners using these products take the proper steps to ensure system wide defense-in-depth strategies, as outlined in Eaton’s whitepaper WP152002EN. This whitepaper can be downloaded at: https://www.eaton.com/content/dam/eaton/products/industrialcontrols-drives-automation-sensors/c441-motor-insight-motor-protection-relays/cyber-security-white-paper-wp152002en.pdf

References (4)

Sources

The same CVE in the primary databases and aggregators, to check against.

Badge for a README or a ticket

CVE-2014-9196 badge
[![CVE-2014-9196](https://trackcve.app/badge/CVE-2014-9196.svg)](https://trackcve.app/cve/CVE-2014-9196)

Record last updated .