CVE-2015-3976

GE Multilink Cross-site Scripting

Medium6.8EPSS 1.2%
Published
Updated
Reserved
Assigned by
icscert

Description

Cross-site scripting (XSS) vulnerability in GE Multilink ML810/3000/3100 series switch 5.2.0 and earlier, and GE Multilink ML800/1200/1600/2400 4.2.1 and earlier.

Scores

CVSS scores of CVE-2015-3976, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)2.0Medium6.8AV:N/AC:L/Au:S/C:N/I:C/A:N
NVDNVD · Modified3.0Medium5.4CVSS:3.0/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N
EPSS (exploitation in 30 days)
1.2% · top 32% of all CVEs (4 Nov 2026)
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: Medium 6.8.

Weakness

Affected products

What to do

Solution: GE recommends users update switch firmware to the latest published version to resolve these vulnerabilities. The new firmware will enable new keys to be calculated and exchanged, resolve the slow data transfer and potential denial of service, and prevent the identified cross-site scripting vulnerabilities. The latest firmware is Version 5.3.2 for the ML800, ML1200, ML1600 and ML2400 and Version 5.3.2-3K for the ML810, ML3000, and ML3100. This firmware is available through the “Resources/Software” link in the product web sites at http://www.gedigitalenergy.com . This firmware is also available through the EnerVista Launchpad device management tool. GE recommends updating the switch over a serial connection to prevent an attacker from capturing the new key. Please refer to the GE advisory for specific information on how to install the firmware and change RSA key. The GE advisory is available at: https://www.gedigitalenergy.com/products/support/multilink/MLSB0415.pdf

References (4)

Sources

The same CVE in the primary databases and aggregators, to check against.

Badge for a README or a ticket

CVE-2015-3976 badge
[![CVE-2015-3976](https://trackcve.app/badge/CVE-2015-3976.svg)](https://trackcve.app/cve/CVE-2015-3976)

Record last updated .