CVE-2016-9154
Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D,…
- Published
- Updated
- Reserved
- Assigned by
- siemens
Description
Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D (All firmware versions < V6.00.046) and Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 for Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U (All firmware versions < V6.00.046) use a pseudo random number generator with insufficient entropy to generate certificates for HTTPS, potentially allowing remote attackers to reconstruct the corresponding private key.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| NVDNVD · Modified | 3.0 | High7.5 | CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N |
- EPSS (exploitation in 30 days)
- 1.5% · top 26% of all CVEs (2 Nov 2026)
Loading the EPSS history…
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.
Weakness
Affected products
Desigo PX Web modules with all firmware versions < V6.00.046
- affected Desigo PX Web modules with all firmware versions < V6.00.046
References (3)
- http://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-856492.pdf (opens in a new tab)x_refsource_CONFIRMx_transferred
- 94962 (opens in a new tab)vdb-entryx_refsource_BIDx_transferred
- https://ics-cert.us-cert.gov/advisories/ICSA-16-355-01 (opens in a new tab)x_refsource_MISCx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Record last updated .