Skip to content
CVE Tracker
Back

CVE-2017-6030

Schneider Electric Modicon PLCs Predictable Value Range from Previous Values

Medium6.5EPSS 2.2%
Published
Updated
Reserved
Assigned by
icscert

Description

A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.

Scores

CVSS scores of CVE-2017-6030, by who scored it
Scored byCVSSScoreVector
CISA-ADPADP (enrichment)3.1Medium6.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L
NVDNVD · Modified3.1Medium6.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L
EPSS (exploitation in 30 days)
2.2% · top 18% of all CVEs (3 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: yes · Technical impact: partial
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: Medium 6.5.

Weakness

Affected products

What to do

Solution: Schneider Electric has released new firmware versions to address the predictable value range from previous values vulnerability and the use of insufficiently random values vulnerability, which are available through Schneider Electric’s software update tool, SoMachine, Version 4.2, and SoMachineBasic, Version 1.5. Schneider Electric has not released a product to address the insufficiently protected credentials vulnerability; however, Schneider Electric has provided compensating controls to reduce the risk of exploitation. SoMachineBasic, Version 1.5, is available at the following location: http://www.schneider-electric.fr/fr/download/document/SOMBASAP15SOFT/  Schneider Electric has provided the following compensating controls to reduce the risk of exploitation of the insufficiently protected credentials vulnerability: * Verify that the hardware and software infrastructure that the PLCs are integrated into (along with all organizational measures and rules covering access to the infrastructure) consider the results of the hazard and risk analysis, and are implemented according to best practices and standards such as ISA/IEC 62443. * Limit traffic on the local network with managed switches * Where possible, avoid using Wi-Fi networks, but when Wi-Fi is essential, use only secure communications (such as WPA2 encryption) * Do not grant [network] access to unknown computers * When remote access is essential, use secure methods such as Virtual Private Networks (VPNs), and ensure the remote access solution(s), as well as the remote computer(s) are kept up-to-date with the latest security patches. Schneider Electric has released Security Notifications SEVD-2017-075-01, SEVD-2017-075-02, and SEVD-2017-075-03, which provide additional information about the identified vulnerabilities, mitigations, and compensating controls: http://www.schneider-electric.com/en/download/document/SEVD-2017-075-01/ http://www.schneider-electric.com/en/download/document/SEVD-2017-075-02/ http://www.schneider-electric.com/en/download/document/SEVD-2017-075-03/

References (3)

Sources

The same CVE in the primary databases and aggregators, to check against.

Badge for a README or a ticket

CVE-2017-6030 badge
[![CVE-2017-6030](https://trackcve.app/badge/CVE-2017-6030.svg)](https://trackcve.app/cve/CVE-2017-6030)

Record last updated .