Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability.…

Critical10.0EPSS 1.3%
Published
Updated
Reserved
Assigned by
mitre

Description

Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.

Scores

CVSS scores of CVE-2017-7574, by who scored it
Scored byCVSSScoreVector
CISA-ADPADP (enrichment)3.1Critical10.0CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:L
NVDNVD · Modified3.1Critical9.8CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS (exploitation in 30 days)
1.3% · top 30% of all CVEs (3 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: yes · Technical impact: total
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: Critical 10.0.