CVE-2020-25178

Rockwell Automation ISaGRAF5 Runtime Cleartext Transmission of Sensitive Information

High7.5EPSS 1.7%
Published
Updated
Reserved
Assigned by
icscert

Description

ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.

Timeline

  1. ID reserved

    By icscert

  2. · 19 months later

    Published

  3. · 3 years later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2020-25178, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)3.1High7.5CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H
NVDNVD · Modified3.1High8.8CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
EPSS (exploitation in 30 days)
1.7% · top 23% of all CVEs (7 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: no · Technical impact: total
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.

Weakness

Affected products

What to do

Solution: Rockwell Automation recommends users update to ISaGRAF Runtime 5 Version 5.72.00. End users are encouraged to restrict or block access on TCP 1131 and TCP 1132 from outside the industrial control system. Confirm the least-privilege user principle is followed and user/service account access to Runtime's folder location is granted with a minimum amount of rights needed. Rockwell Automation recommends users of affected versions evaluate the mitigations provided and apply the appropriate mitigations to deployed products. Users are encouraged to combine this guidance with the general security guidelines for a comprehensive defense-in-depth strategy. To reduce risk, Rockwell Automation recommends users: Employ proper network segmentation and security controls. Minimize network exposure for all control system devices. Locate control systems behind firewalls. Isolate control systems from other networks when possible. Refer to the Converged Plantwide Ethernet (CPwE) Design and Implementation Guide for best practices deploying network segmentation and broader defense-in-depth strategies. Consider using proper network infrastructure controls, such as firewalls, UTM devices, VPN, or other security appliances. Ensure the least-privilege user principle is followed, and user/service account access to Runtime’s folder location is granted with a minimum amount of rights, as needed. Please see publications from Rockwell Automation and Schneider Electric, Xylem, or contact GE for further information about how to mitigate these vulnerabilities in additional affected products.