An unauthenticated remote attacker can send data to RsvcHost.exe listening on TCP port 5241 to add entries in the FactoryTalk Diagnostics…
High7.5EPSS 39.3%
- Published
- Updated
- Reserved
- Assigned by
- tenable
Description
An unauthenticated remote attacker can send data to RsvcHost.exe listening on TCP port 5241 to add entries in the FactoryTalk Diagnostics event log. The attacker can specify long fields in the log entry, which can cause an unhandled exception in wcscpy_s() if a local user opens FactoryTalk Diagnostics Viewer (FTDiagViewer.exe) to view the log entry. Observed in FactoryTalk Diagnostics 6.11. All versions of FactoryTalk Diagnostics are affected.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| NVDNVD · Modified | 3.1 | High7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
- EPSS (exploitation in 30 days)
- 39.3% · top 1.4% of all CVEs (6 Nov 2026)
Loading the EPSS history…
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.
Weakness
- Unauthenticated Remote Denial of Service
- CWE-755 (opens in a new tab)All about CWE-755 and its CVEs
Affected products
Rockwell FactoryTalk Diagnostics
- affected All versions of FactoryTalk Diagnostics
References (1)
- https://www.tenable.com/security/research/tra-2020-71 (opens in a new tab)x_refsource_CONFIRMx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://trackcve.app/cve/CVE-2020-5807)Record last updated .