CVE-2022-2004
AutomationDirect DirectLOGIC with Ethernet Communication Uncontrolled Resource Consumption
- Published
- Updated
- Reserved
- Assigned by
- icscert
Description
AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| icscertCNA (assigner) | 3.1 | High7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| NVDNVD · Modified | 3.1 | High7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
- EPSS (exploitation in 30 days)
- 1.0% · top 36% of all CVEs (3 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: yes · Technical impact: partial
Loading the EPSS history…
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.
Weakness
Affected products
AutomationDirect · DirectLOGIC D0-06 series CPUs
- affected D0-06DD1 – < 2.72
- affected D0-06DD2 – < 2.72
- affected D0-06DR – < 2.72
- affected D0-06DA – < 2.72
- affected D0-06AR – < 2.72
- affected D0-06AA – < 2.72
- affected D0-06DD1-D – < 2.72
- affected D0-06DD2-D – < 2.72
- affected D0-06DR-D – < 2.72
What to do
Solution: AutomationDirect recommends users upgrade to firmware Version 2.72 or later for all DL06 CPUs for CVE-2022-2002. Additional brute force mitigation for password access has also been added. Three incorrect password entries will result in a three hour lock out of password entry. Power cycle will allow subsequent password attempts. Please see the security network practices below for CVE-2022-2004. While automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application. AutomationDirect has identified the specific mitigation actions listed below: Secure physical access. Isolate and air gap networks when possible. Consider some of the AutomationDirect newer PLC families.
References (1)
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03 (opens in a new tab)x_refsource_CONFIRMx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Record last updated .