Skip to content
CVE Tracker
Back

CVE-2022-2005

AutomationDirect C-more EA9 HMI Cleartext Transmission

High7.5EPSS 0.55%
Published
Updated
Reserved
Assigned by
icscert

Description

AutomationDirect C-more EA9 HTTP webserver uses an insecure mechanism to transport credentials from client to web server, which may allow an attacker to obtain the login credentials and login as a valid user. This issue affects: AutomationDirect C-more EA9 EA9-T6CL versions prior to 6.73; EA9-T6CL-R versions prior to 6.73; EA9-T7CL versions prior to 6.73; EA9-T7CL-R versions prior to 6.73; EA9-T8CL versions prior to 6.73; EA9-T10CL versions prior to 6.73; EA9-T10WCL versions prior to 6.73; EA9-T12CL versions prior to 6.73; EA9-T15CL versions prior to 6.73; EA9-RHMI versions prior to 6.73; EA9-PGMSW versions prior to 6.73;

Scores

CVSS scores of CVE-2022-2005, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)3.1High7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
NVDNVD · Modified3.1High7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
EPSS (exploitation in 30 days)
0.55% · top 54% of all CVEs (4 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: yes · Technical impact: partial
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.

Weakness

Affected products

  • AutomationDirect · C-more EA9

    • affected EA9-T6CL – < 6.73
    • affected EA9-T6CL-R – < 6.73
    • affected EA9-T7CL – < 6.73
    • affected EA9-T7CL-R – < 6.73
    • affected EA9-T8CL – < 6.73
    • affected EA9-T10CL – < 6.73
    • affected EA9-T10WCL – < 6.73
    • affected EA9-T12CL – < 6.73
    • affected EA9-T15CL – < 6.73
    • affected EA9-RHMI – < 6.73
    • affected EA9-PGMSW – < 6.73

What to do

Solution: AutomationDirect recommends users upgrade to firmware Version 6.73 or later, which supports TLS security options for the webserver. While automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application. AutomationDirect has identified the following mitigations for instances where systems cannot be upgraded to Version 6.73 or later: The Webserver feature can be disabled on the HMI using the programming software. Place the HMI panel behind a VPN: Access to and from critical control system assets in the modern environment is usually LAN based, but still should be considered remote if the operator is traversing across different networks. virtual private networking (VPN) is often considered the best approach in securing trans-network communication.