Skip to content
TrackCVE
  • Newest CVEsPage
  • Recently added to KEVPage
  • Rising exploitation (EPSS)Page
  • Weekly digestPage
  • StatisticsPage
  • WatchlistPage
  • API documentationPage
  • MCP serverPage
  • Data sourcesPage
  • ChangelogPage
  • AboutPage
  • How it's builtPage
Back

CVE-2022-2105

Secheron SEPCOS Control and Protection Relay

Critical9.4EPSS 1.1%
Published
Updated
Reserved
Assigned by
icscert

Description

Client-side JavaScript controls may be bypassed to change user credentials and permissions without authentication, including a “root” user level meant only for the vendor. Web server root level access allows for changing of safety critical parameters.

Timeline

  1. ID reserved

    By icscert

  2. · 8 days later

    Published

  3. · 3 years later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2022-2105, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)3.1Critical9.4CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H
NVDNVD · Modified3.1Critical9.1CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H
EPSS (exploitation in 30 days)
1.1% · top 34% of all CVEs (7 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: yes · Technical impact: partial
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: Critical 9.4.

Weakness

Affected products

What to do

Solution: Secheron recommends updating its software to the latest version: SEPCOS Single Package firmware (1.23.xx feature level): Update to 1.23.22 or higher version SEPCOS Single Package firmware (1.24.xx feature level): Update to 1.24.8 or higher version SEPCOS Single Package firmware (1.25.xx feature level): Update to 1.25.3 or higher version

Workaround: Additional workarounds are suggested to help reduce the risk: Configure the network such that PLC communications are strictly limited to only the devices required to perform its functions. Limit remote access and close Ports 80 and 443 at the switch level. Only use approved devices to connect to the PLCs. Do not connect personal peripherals (USB sticks, hotspots) to approved devices. Check device logs during periodic maintenance for unauthorized changes or access.

References (1)

Sources

The same CVE in the primary databases and aggregators, to check against.

Badge for a README or a ticket

CVE-2022-2105 badge
[![CVE-2022-2105](https://trackcve.app/badge/CVE-2022-2105.svg)](https://trackcve.app/cve/CVE-2022-2105)

Record last updated .