CVE-2022-2513

Cleartext Credentials Vulnerability on Hitachi Energy’s Multiple IED Connectivity Packages (IED ConnPacks) and PCM600 Products

High7.1EPSS 0.16%
Published
Updated
Reserved
Assigned by
Hitachi Energy

Description

A vulnerability exists in the Intelligent Electronic Device (IED) Connectivity Package (ConnPack) credential storage function in Hitachi Energy’s PCM600 product included in the versions listed below, where IEDs credentials are stored in a cleartext format in the PCM600 database and logs files. An attacker having get access to the exported backup file can exploit the vulnerability and obtain user credentials of the IEDs. Additionally, an attacker with administrator access to the PCM600 host machine can obtain other user credentials by analyzing database log files. The credentials may be used to perform unauthorized modifications such as loading incorrect configurations, reboot the IEDs or cause a denial-of-service on the IEDs.

Timeline

  1. ID reserved

    By Hitachi Energy

  2. · 4 months later

    Published

  3. · 3 years later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2022-2513, by who scored it
Scored byCVSSScoreVector
Hitachi EnergyCNA (assigner)3.1High7.1CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N
NVDNVD · Modified3.1Medium5.5CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N
EPSS (exploitation in 30 days)
0.16% · top 95% of all CVEs (7 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: no · Technical impact: partial
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.1.

Weakness

Affected products

What to do

Solution: Update to PCM600 v2.11 Hotfix 20240426 or apply mitigation factors/workarounds as described in the Mitigation Factors/Workarounds Section. List of CPEs:  cpe:2.3:a:hitachienergy:pcm600:*:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.4.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.3.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.2.6:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.1.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.0.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:2.4.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:2.3.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:2.2.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:2.1.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:1.3.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:sam600ioConnectivityPackage:1.2.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:sam600ioConnectivityPackage:1.1.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:sam600ioConnectivityPackage:1.0.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:pwc600ConnectivityPackage:1.3.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:pwc600ConnectivityPackage:1.2.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:pwc600ConnectivityPackage:1.1.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:pwc600ConnectivityPackage:1.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:pwc600ConnectivityPackage:1.1.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:gms600ConnectivityPackage:1.3.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:gms600ConnectivityPackage:1.3.0:*:*:*:*:*:*:*

Workaround: It is recommended to implement and continuously revise least privileges principles to minimize permissions and accesses to PCM600 related resources, included the backup file, PCMI/PCMP file. Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. An additional recommendation is to follow the hardening guidelines published by “The Center for Internet Security (CIS)” https://www.cisecurity.org/about-us/ to protect the host Operating System. More information to deploy PCM600 securely can be found in the following documents: 1MRS758440, PCM600 Cyber Security Deployment Guideline

References (1)

Sources

The same CVE in the primary databases and aggregators, to check against.

Badge for a README or a ticket

CVE-2022-2513 badge
[![CVE-2022-2513](https://trackcve.app/badge/CVE-2022-2513.svg)](https://trackcve.app/cve/CVE-2022-2513)

Record last updated .