CVE-2022-29922
A vulnerability exists in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS ...
- Published
- Updated
- Reserved
- Assigned by
- Hitachi Energy
Description
Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Timeline
ID reserved
By Hitachi Energy
- 5 months later
· 5 months later
Published
- 3 years later
· 3 years later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| Hitachi EnergyCNA (assigner) | 3.1 | High7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| NVDNVD · Modified | 3.1 | High7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
- EPSS (exploitation in 30 days)
- 0.79% · top 43% of all CVEs (7 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: yes · Technical impact: partial
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.
Weakness
Affected products
Hitachi Energy · MicroSCADA X SYS600
- affected 10
- affected 10.1
- affected 10.1.1
- affected 10.2
- affected 10.2.1
- affected 10.3
- affected 10.3.1
Hitachi Energy · MicroSCADA Pro SYS600
- affected unspecified – ≤ 9.2 FP2 Hotfix 4
What to do
Solution: Remediated in SYS600 10.4 For MicroSCADA Pro SYS600 - Upgrade to at least SYS600 version 10.4. For MicroSCADA X SYS600 - Update to at least SYS600 version 10.4.
Workaround: Apply general mitigation factors as specify in the advisory.
References (1)
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://trackcve.app/cve/CVE-2022-29922)Record last updated .