Back
CVE-2022-33174
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web…
Critical9.8EPSS 14.1%
- Published
- Updated
- Reserved
- Assigned by
- mitre
Description
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| mitreCNA (assigner) | 3.1 | Critical9.8 | CVSS:3.1/AC:L/AV:N/A:H/C:H/I:H/PR:N/S:U/UI:N |
| NVDNVD · Modified | 3.1 | High7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N |
- EPSS (exploitation in 30 days)
- 14.1% · top 3.4% of all CVEs (6 Nov 2026)
Loading the EPSS history…
The list uses the assigner's score when there is one, then CISA's, then NVD's: Critical 9.8.
Weakness
Affected products
n/a
- affected n/a
References (1)
- https://gynvael.coldwind.pl/?lang=en&id=748 (opens in a new tab)x_refsource_MISCx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://trackcve.app/cve/CVE-2022-33174)Record last updated .