CVE-2025-26385
Metasys product command injection vulnerability could allow remote SQL execution
- Published
- Updated
- Reserved
- Assigned by
- jci
Description
Johnson Controls Metasys component listed below have Improper Neutralization of Special Elements used in a Command (Command Injection) Vulnerability . Successful exploitation of this vulnerability could allow remote SQL execution This issue affects * Metasys: Application and Data Server (ADS) installed with SQL Express deployed as part of the Metasys 14.1 and prior installation, * Extended Application and Data Server (ADX) installed with SQL Express deployed as part of the Metasys 14.1 installation, * LCS8500 or NAE8500 installed with SQL Express deployed as part of the Metasys installation Releases 12.0 through 14.1, * System Configuration Tool (SCT) installed with SQL Express deployed as part of the SCT installation 17.1 and prior, * Controller Configuration Tool (CCT) installed with SQL Express deployed as part of the CCT installation 17.0 and prior.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| jciCNA (assigner) | 4.0 | Critical9.5 | CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H |
| NVDNVD · Deferred | 4.0 | Critical9.5 | CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
- EPSS (exploitation in 30 days)
- 1.5% · top 26% of all CVEs (7 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: yes · Technical impact: total
The list uses the assigner's score when there is one, then CISA's, then NVD's: Critical 9.5.
Weakness
Affected products
- affected Application and Data Server (ADS) installed with SQL Express deployed as part of the Metasys 14.1 and prior installation
- affected Extended Application and Data Server (ADX) installed with SQL Express deployed as part of the Metasys 14.1 installation
- affected LCS8500 or NAE8500 installed with SQL Express deployed as part of the Metasys installation Releases 12.0 through 14.1
- affected System Configuration Tool (SCT) installed with SQL Express deployed as part of the SCT installation 17.1 and prior
- affected Controller Configuration Tool (CCT) installed with SQL Express deployed as part of the CCT installation 17.0 and prior
What to do
Solution: a. Follow the Johnson Controls hardening guide steps to ensure your Metasys installation is on a segmented network, not exposed to untrusted networks such as the internet b. Download and execute the Metasys patch for GIV-165989 from the License Portal https://software.jci.com/licenseportal/ . Login credentials are required c. Close incoming TCP port 1433 d. For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2026-02 at the following location: https://www.johnsoncontrols.com/cyber-solutions/security-advisories
References (2)
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://trackcve.app/cve/CVE-2025-26385)Record last updated .