CVE-2025-59484
AutomationDirect CLICK PLUS Use of a Broken or Risky Cryptographic Algorithm
- Published
- Updated
- Reserved
- Assigned by
- icscert
Description
The use of a broken or risky cryptographic algorithm was discovered in firmware version 3.60 of the Click Plus PLC. The vulnerability relies on the fact that the software uses an insecure implementation of the RSA encryption algorithm.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| icscertCNA (assigner) | 4.0 | High8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:L/SC:N/SI:N/SA:N |
| icscertCNA (assigner) | 3.1 | High8.3 | CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:L |
| NVDNVD · Deferred | 4.0 | High8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
- EPSS (exploitation in 30 days)
- 0.12% · top 98% of all CVEs (5 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: no · Technical impact: total
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 8.7.
Weakness
Affected products
AutomationDirect · CLICK PLUS C0-0x CPU firmware
- affected < v3.71
AutomationDirect · CLICK PLUS C0-1x CPU firmware
- affected < v3.71
AutomationDirect · CLICK PLUS C2-x CPU firmware
- affected < v3.71
What to do
Solution: AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80. https://www.automationdirect.com/support/software-downloads If the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed: * Network Isolation – Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure. * Secure Communications – Use only trusted, dedicated internal networks or air-gapped systems for device communication. * Access Control – Restrict both physical and logical access to authorized personnel only. * Application Whitelisting – Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software. * Endpoint Protection – Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts. * Logging & Monitoring – Enable and regularly review system logs to detect suspicious or unauthorized activity. * Backup & Recovery – Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident. * Ongoing Risk Assessment – Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.
References (2)
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)